RS232 Communication Industrial UPS Power Supply
3ph / 1ph 10-100KVA
Industrial Grade Design:
The CNI310 system is composed of power special-purpose UPS, DBW regulator cabinet, PDU series feeder cabinet. CONSNANT Company apply herself to the development of China’s electricity demands for power plants, substations, power distribution products are designed with online double conversion, zero conversion function. Main applications including electric power long distance, RTU, power carrier wave, power monitoring and so on. When the utility power is normal, single phase 220V. After isolation, rectification and filtering through the inverter to provide a stable power supply to the load; if the input AC power is abnormal or power failure, the backup power system by the DC screen provide power through non-return diode inverter. When the DC screen occurs voltage shortage or power break, the static switch transfer to bypass for power supply; when the electricity is restored, the inverter automatically switches to utility power and provide power supply under inverter mode. If the inverter overload or fault and transfer power supply is under bypass mode, UPS also gives a warning signal at the same time.
System Features:
Protection degree is IP42, highly protecting the electronics inside the cabinet. Efficiency smartmode up to 98%, save power consumption and improve environment protection. CNI310 meet with EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC), qualitication ensured.
Application:
Petroleum, chemical industry, gas and power station and so on.
Optional Spare Part:
FAQ:
Q1: What's included in products?
A: It is included UPS unit, user manual, 2% spare parts for emergency, test certificate(optional)
Q2. Your UPS meet CE requirements?
A:Our UPS is with the certificate of CE, ISO and .Chinese TLC certificates.
Q3: Can we change the shape, size, color or printing based on the original design?
A: Yes, and OEM, ODM accepted
Q4:. Can you design one specially?
A: Yes
Technical parameter:
CNI310 10-100KVA | ||||||||
Model | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA |
Capacity | 8KW | 12KW | 16KW | 24KW | 32KW | 48KW | 64KW | 80KW |
Input | ||||||||
Rated voltage | 380/400/415 Vac three | |||||||
Voltage range | ±20% | |||||||
Frequency range | 50/60HZ±5% | |||||||
Power factor | ≥0.8 | |||||||
Current harmonic distortion | <5%with harmonic filter | |||||||
Soft start | 0-100% in 10” | |||||||
Bypass Input | ||||||||
Rated voltage | 220/230/240Vac single-phase | |||||||
Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||
Rated frequency | 50/60Hz | |||||||
Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||
Standard features | BackFeed protection; split bypass line | |||||||
Batteries | ||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||
Maximum recharge current(A) | 0.2 X C10 | |||||||
DC Voltage | 384VDC | |||||||
AC ripple voltage | <1% | |||||||
Inverter output | ||||||||
Number of phase | 1 | |||||||
Rated voltage(V) | 230Vac single phase | |||||||
Regulation of the output voltage | 220~244Vac phase/neutral(from control panel) | |||||||
Crest factor (Ipeak/Irms) |
3:1 | |||||||
Static stability | ±1% | |||||||
Dynamic stability | ±5% | |||||||
Frequncy | 50/60Hz configurable | |||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||
Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present |