Optional SNMP Card Industrial UPS Power Supply With High Grade Protection
Application:
Petroleum, chemical industry, gas and power station and so on.
Key features:
System:
Technical parameter:
CNI310 10-100KVA | ||||||||
Model | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA |
Capacity | 8KW | 12KW | 16KW | 24KW | 32KW | 48KW | 64KW | 80KW |
Input | ||||||||
Rated voltage | 380/400/415 Vac three | |||||||
Voltage range | ±20% | |||||||
Frequency range | 50/60HZ±5% | |||||||
Power factor | ≥0.8 | |||||||
Current harmonic distortion | <5%with harmonic filter | |||||||
Soft start | 0-100% in 10” | |||||||
Bypass Input | ||||||||
Rated voltage | 220/230/240Vac single-phase | |||||||
Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||
Rated frequency | 50/60Hz | |||||||
Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||
Standard features | BackFeed protection; split bypass line | |||||||
Batteries | ||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||
Maximum recharge current(A) | 0.2 X C10 | |||||||
DC Voltage | 384VDC | |||||||
AC ripple voltage | <1% | |||||||
Inverter output | ||||||||
Number of phase | 1 | |||||||
Rated voltage(V) | 230Vac single phase | |||||||
Regulation of the output voltage | 220~244Vac phase/neutral(from control panel) | |||||||
Crest factor (Ipeak/Irms) |
3:1 | |||||||
Static stability | ±1% | |||||||
Dynamic stability | ±5% | |||||||
Frequncy | 50/60Hz configurable | |||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||
Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||
System | ||||||||
Remote signaling | Volt free contacts | |||||||
Remote controls | EPO and Bypass | |||||||
Communication | RS232 + remote contacts | |||||||
Weight(KG)N.M | 200 | 220 | 230 | 260 | 290 | 340 | 440 |