  • AC In. Volt.
    380×(1±15%)V
  • AC In. Frequency
    50×(1±1%)Hz
  • Relative Humidity
    <90%(25℃)
  • Display Accuracy
    ±2%FS
  • Output Current Capacity(A)
    45/75/100/150/200
  • AC Input Topology
    Three-phase Three-wire
  • Place of Origin
    Shenzhen China
  • Brand Name
    CONSNANT
  • Certification
    ISO CE
  • Model Number
    50A - 300A
  • Minimum Order Quantity
    10
  • Packaging Details
    export standard carton box
  • Payment Terms
    L/C, T/T, Western Union

APF Active Power Filter Multi - Parameter Display Simul Compensation Of Harmonic

Multi - Parameter Display APF Active Power Filter Simul Compensation Of Harmonic

 

 

Features:

 

1 Neutral current first compensating, simultaneous compensation of Harmonic and reactive power

2 Order of harmonic selectable compensating

3 System parameter settings online

4 RS485 standard, Modbus RTU remote control function communication protocol

5 Automatically or manually working Mode 
6 Operation Display: LCD monitoring panel; parameters setting online; touchable button operation; multi-parameter display
7 Expansion Ability:  directly connect in parallel with the same model machine
8 Protection: Grid over-voltage, Grid under-voltage, Grids missing phase, Grid wrong phase, the Machine over current and overheating

 

 

Why Choose Us?

 

  • We have experienced team for more ten years and high-tech equipment.
  • Our products is with ICE, ISO and Chinese TLC
  • We can make product according to your requirements, such as your size, color, design, and your logo.
  • We can offer you very competitive price.
  • You can get expert guides from us all the time.

 

 

Technical Specification:

 

Output current capacity(A) 45 75 100 150 200

AC

Input

Rated voltage 380×(1±15%)V
Rated Frequency 50×(1±1%)Hz
Rated topology Three-phase three-wire

Technical
Indexes

 

Orders of harmonic compensating

Within 5~13: selectable

Or within 5~25: all compensation

Compensating rate (THDILoad-THDIS)/ THDILoad ≥85%
Reactive power compensating

Determined by priority

 

Full response time ≤20ms
Overload Protection Automatically limited to the rated output current
Active power loss <5%Rated capacity
Noise <65dB

Environment

&
Conditions

Operating temperature -10OC~+45OC
Storing temperature -20OC~+65OC
Relative humidity <90%(25OC)
Protection level IP20
dimension mm(W×H×D) 600×1200×400 600×2200×600 800×2200×600
Non-standard sizes can be customized