Multi - Parameter Display APF Active Power Filter Simul Compensation Of Harmonic
Features:
1 Neutral current first compensating, simultaneous compensation of Harmonic and reactive power
2 Order of harmonic selectable compensating
3 System parameter settings online
4 RS485 standard, Modbus RTU remote control function communication protocol
5 Automatically or manually working Mode
6 Operation Display: LCD monitoring panel; parameters setting online; touchable button operation; multi-parameter display
7 Expansion Ability: directly connect in parallel with the same model machine
8 Protection: Grid over-voltage, Grid under-voltage, Grids missing phase, Grid wrong phase, the Machine over current and overheating
Why Choose Us?
Technical Specification:
Output current capacity(A) | 45 | 75 | 100 | 150 | 200 | |
AC Input |
Rated voltage | 380×(1±15%)V | ||||
Rated Frequency | 50×(1±1%)Hz | |||||
Rated topology | Three-phase three-wire | |||||
Technical
|
Orders of harmonic compensating |
Within 5~13: selectable Or within 5~25: all compensation |
||||
Compensating rate (THDILoad-THDIS)/ THDILoad | ≥85% | |||||
Reactive power compensating |
Determined by priority
|
|||||
Full response time | ≤20ms | |||||
Overload Protection | Automatically limited to the rated output current | |||||
Active power loss | <5%Rated capacity | |||||
Noise | <65dB | |||||
Environment & |
Operating temperature | -10OC~+45OC | ||||
Storing temperature | -20OC~+65OC | |||||
Relative humidity | <90%(25OC) | |||||
Protection level | IP20 | |||||
dimension mm(W×H×D) | 600×1200×400 | 600×2200×600 | 800×2200×600 | |||
Non-standard sizes can be customized | ||||||
Weight(kg) | 150 | 200 | 400 |