Shenzhen Consnant Technology Co., Ltd. 86-755-29772322 sales@consnant.com
Electricity Online UPS |CND310 10 – 100KVA 380/400/415VAC 220VDC  anti-overload  digital control  user-friendly

Electricity Online UPS |CND310 10 – 100KVA 380/400/415VAC 220VDC anti-overload digital control user-friendly

  • Capacity
    160 – 250KVA
  • Nominal Capacity
    10 – 100KVA
  • Nominal Voltage
    380/400/415VAC
  • Maximum Input Voltage Range
    +-25%
  • Nominal Frequency
    50/60HZ
  • DC Voltage
    220VDC
  • Place of Origin
    Shenzhen, China
  • Brand Name
    CONSNANT
  • Certification
    CE, ISO9001, ISO14001,ISO45001
  • Model Number
    CND310 10-100KVA
  • Minimum Order Quantity
    10
  • Price
    Negotiable
  • Packaging Details
    Export Standard Package
  • Delivery Time
    5-7 days for sample order, 7-15 days for mass production
  • Payment Terms
    T/T, L/C, Western Union
  • Supply Ability
    50000 pieces per year

Electricity Online UPS |CND310 10 – 100KVA 380/400/415VAC 220VDC anti-overload digital control user-friendly

Electricity Online UPS |CND310 10 – 100KVA 380/400/415VAC 220VDC anti-overload digital control user-friendly

 

Application field:

  • Petrochemical industry
  • natural gas industry
  • power plant
  • power station

 

Description:

 

The CND310 series Electricity Special UPS system consisting of system cabinet, DBW bypass stabilized cabinet, and PDU feeder cabinet;

 

CONSNANT designs exclusively for power plant, transformer substation, and distribution substation according to the development requirement of China Power.

 

It possesses on-line double conversion and zero transfer function.

 

It can be mainly applied for power system telemechanics, PTU, power line carrier, power system monitoring and so on.

 

After being isolated and filtered by regulator, Single-phase 220V or three-phase 380V can provide stable power for load through inverter when the AC is normal.

 

If the failure of AC power grid supply or a power cut occurs, the backup of DC power system can invert to supply electricity through the reverse diode.

 

If the DC Power System is under voltage or cut off, the static switch will turn to bypass automatically. When the AC power is recover, the static switch will turn to AC power automatically.

 

If the inverter is overloaded or fault, the system will turn to bypass and indicates a warning signal at the same time.

 

Features:

 

Adopt full digital control technology

 

Intelligent detection and monitoring function

 

Digitally control the static switching with zero switch

 

Full isolation between input and output

 

Super low output zero earth voltage

 

DC UPS isolated with utility power Compatible with the DC power system and isolated with utility power completely

 

Cubicle design with the power standard both indication and cabinet (Can be customized according to customer demands)

 

Multifunctional protection for over voltage, under voltage, over current, short circuit and over temperature and so on.

 

Large-screen LCD monitor with Chinese and English operation interface

 

Ultralong 256 event record, user-friendly analysis and management to the situation of the power supply (touch screen optional)

 

Static bypass has a strong anti-overload capability

 

Model Number 10KVA 15KVA 20KVA 30KVA 40KVA
Rating capacity 8 KW 12 KW 16 KW 24 KW 32 KW
Rating voltage 220VAC Single Phase (6-20KVA) / 380VAC Three Phases
AC input
Voltage range ±25%
Frequency range 50/60Hz±10%
Soft start 0 – 100% 5 seconds
Power Factor 0.95(with input filter)
Bypass input
Permitted voltage
range
±15%
Frequency range 50/60Hz±5%
Output
Voltage accuracy 220V±1%(steady load) 220V±3%( fluctuating load)
Permitted Frequency
range
50/60Hz±0.05Hz(powered by battery)
Power factor 0.8
Waveform Distorition Linearload<2%, non linear load<4%
Dynamic load
voltage transients
<5%
Crest factor(lpeak/
lrms)
3:01
Overload capacity Normal in 110% load, 125% for 10min
Efficiency Double conversion mode: 94%; ECO mode: 98%
DC
Battery voltage 220V; (10-40KVA 110V is optional)
Cutoff voltage 185V
Maximum discharge
current
36A 55A 73A 109A 145A
Panel display
LCD Chinese/English UPS status, operation instruction input voltage, output voltage, current, frequency, battery voltage, value of charge and discharge
current, fault display , warning
Environment
Temperature 0ºC-40 ºC
Humidity 0-95%(no condensing)
Storage temperature -25 ºC—55 ºC
Altitude <1500m
Physical features
Weight(KG) Net 230 258 350 400 480
Gross 250 285 380 425 500
Dimesion
W X D X H mm
800×600×2260 800×800×2260
Optional RS485/SNMP/ Harmonic compensation cabinet/Input and output isolation cabinet/Lightning protection device/Bypass stablelized cabinet/
Customized appearance and size

 

Model Number 50KVA 60KVA 80KVA 100KVA
Rating capacity 40 KW 48 KW 64 KW 80 KW
Rating voltage 220VAC Single Phase (6-20KVA) / 380VAC Three Phases
AC input
Voltage range ±25%
Frequency range 50/60Hz±10%
Soft start 0 – 100% 5 seconds
Power Factor 0.95(with input filter)
Bypass input
Permitted voltage
range
±15%
Frequency range 50/60Hz±5%
Output
Voltage accuracy 220V±1%(steady load) 220V±3%( fluctuating load)
Permitted Frequency
range
50/60Hz±0.05Hz(powered by battery)
Power factor 0.8
Waveform Distorition Linearload<2%, non linear load<4%
Dynamic load
voltage transients
<5%
Crest factor(lpeak/
lrms)
3:01
Overload capacity Normal in 110% load, 125% for 10min
Efficiency Double conversion mode: 94%; ECO mode: 98%
DC
Battery voltage 220V; (10-40KVA 110V is optional)
Cutoff voltage 185V
Maximum discharge
current
181A 218A 291A 364A
Panel display
LCD Chinese/English UPS status, operation instruction input voltage, output voltage, current, frequency, battery voltage, value of charge and discharge
current, fault display , warning
Environment
Temperature 0ºC-40 ºC
Humidity 0-95%(no condensing)
Storage temperature -25 ºC—55 ºC
Altitude <1500m
Physical features
Weight(KG) Net 580 650 900 950
Gross 600 675 925 988
Dimesion
W X D X H mm
800×800×2260 800×1200×2260
Optional RS485/SNMP/ Harmonic compensation cabinet/Input and output isolation cabinet/Lightning protection device/Bypass stablelized cabinet/
Customized appearance and size