220VAC distributed power system, single-phase lithium DPS, Lithium-ion IDC DPS 220VAC
Application field
Power supply application scenarios such as distributed data centers, load-bearing limited data centers, phased deployment of data centers, rapid deployment of data centers, and integrated cabinets.
Power range: 1KVA – 10KVA (1PH/1PH)
Performance characteristics
☆ Intelligent detection, battery type optional, output shunt timing control
Intelligent detection of fan and capacitor running time
4 output shunts support timing control function
Battery type: lead-acid battery, lithium-ion battery, ternary lithium battery, and custom battery type
☆ Reliable, intelligent, and fast deployment
Intelligent detection of running time of fans and capacitors;
Dual 220VAC input, dual 220VAC output, can intelligently detect the power of other equipment (optional).
☆ Effective use of space and load-bearing
The weight of the equipment is equivalent to that of the server, and the weight-bearing only needs 500Kg/m2;
The deployment does not require independent distributed power system space and battery room, and the number of effective cabinets has increased by more than 40%;
☆ Energy-saving and emission reduction, cabinet-level energy management effectively combined with cloud computing
High-efficiency power supply module, the efficiency of the whole series of products is as high as 94%;
Full lithium battery backup system, discharge efficiency up to more than 97%, life span up to 10 years;
Each output can be selected for time-sharing control. With the energy management system, it can achieve cabinet-level energy management and coordinate with cloud computing for scheduling;
☆ Power supply host, modular design of lithium-ion battery, hot-swappable, easy installation and maintenance
The product is designed and produced in a modular manner. The power supply host and the iron-lithium battery are independent modules. They support hot swapping while ensuring that the power equipment does not lose power; small in size, light weight, and can be completed by one person.
☆ Conducive to the user's demand for a low "PUE" value
The distributed power supply mode divides the power consumption of the traditional large UPS into the cabinet and reduces the PUE value.
Technical parameter
Model | DPS-1103A | DPS-1106A | DPS-1110A |
Capacity | 3000VA / 2700W | 6000VA / 5400W | 10000VA / 9000W |
Input | |||
Input voltage | 220VAC | ||
Voltage Range | 176-250Vac @ (80-100%) load | ||
Frequency Range | 46Hz - 54Hz @ 50Hz system; 56Hz - 64Hz @ 60Hz system | ||
Power Factor | ≧ 0.99 | ||
Output | |||
Output voltage | 208/220/230/240VAC | ||
Voltage accuracy | ±1% (battery mode) | ||
Frequency range | 46Hz - 54Hz @ 50Hz system; 56Hz - 64Hz @ 60Hz system (Synchronization range) | ||
Frequency range | 50Hz±0.1Hz or 60Hz±0.1Hz(battery mode) | ||
Power factor | ≧ 0.9 | ||
Crest factor | 3:1 Max. | ||
Harmonic distortion | ≦2% @ 100% linear load; ≦3% @ 100% non-linear load | ||
Transfer time | 0 ms (AC mode); 0 ms (Inverter Mode); ﹤10 ms (Inverter ECO) | ||
Run | |||
Input and output | 1 line input & 2 lines output or 2 lines input & 2 lines output | ||
Efficiency | |||
Inverter Mode | ﹥ 94% | ||
Battery | |||
Battery type | 192/230V lithium battery | ||
Battery capacity | 10AH/12AH/15AH/18AH/20AH/25AH/30AH | ||
Appearance | |||
Dimension D × W × H (mm) |
800 ×438 ×88(2U) Power Host 800 ×438 ×176(4U)/264(6U) include the lithium battery |
||
Net Weight (kg) | 28 (power host) | ||
Environment | |||
Storage temperature | -25 ℃ - 55 ℃ | ||
Working temperature | 0 ℃ - 45 ℃ | ||
Working altitude | ﹤ 2000 m | ||
Working humidity | ﹤95% No condensation | ||
Working noise | ﹤55dB @ 1 meter distance | ||
Management | |||
Intelligent slot | Support Window@2000/2003/XP/Vista/2008,Window @7/8, Linux and MAC | ||
Optional | Support SNMP CARD |
* The output efficiency will be reduced to 60% when CVCF mode;
* The output power will be reduced to 90% when the output voltage is set to 208VAC.