IP55 Telecom Outdoor Online UPS with AGM/GEL Battery 1-10KVA
Key Features:
Capacity: 1-10KVA
Nominal voltage: 220/230/240VAC
Nominal frequency: 50/60Hz
Output Power factor: 0.7/0.8
Reliable power Rich experience:
CNW110 series communication marginal network outdoor UPS is special for wireless communication system of outdoor micro cellular base station and design of a high-performance integrated outdoor online uninterrupted power supply system, has the very high technology advancement and practicability.
Key Features:
1. Consnant Outdoor Intelligent High Frequency Online UPS provide continuous pure sine wave AC power supply for outside communications / network equipment.
2. Double-conversion online design, high temperature resistant, anti-cold, sealing level for IP55; With the wide range of input voltage and frequency of input window (-45% +35% rated voltage and ± 10% rated frequency), in many remote areas of China after a severe test of the grid.
Application:
This UPS is commonly used in the corner of the city, remote roads, mountains, bad environment, such as high temperature (+50 °C) / low temperature (-40 °C), severe dust, moisture,rain, mist erosion, very poor power quality (voltage longterm higher than 260V or less than 160V, frequency abnormal change) in the area.
High Reliability of the UPS System:
Using microprocessor control, directly produce highfrequency pulse width modulation wave (SPWM) control of the UPS inverter, to simplify the UPS control circuit, to improve the stability, to have more real-time UPS to quickly respond to changes in the external environment and guarantee the machine's control circuit is more simple and reliable.
Using digital control techniques, to avoid the traditional analog control temperature drift inherent defects such as hardware parameters, to ensure consistency and reliability of UPS.
Fine dust-proof, water-proof features:
According to the overall standard of design dust-proof and water-proof Ip55
With a sun protection, heat insulation, roof ventilation
With waterproof and the filtration dust inlet; the cabinet front door shutters with waterproof design, on the back of welding water tank, water tank installed above the net with quick release feature of the dust.
Environmental adaptability:
1. Wide input voltage, avoids frequent switching to battery power because of large power grid voltage, reduce battery failure probability, adapt to the power environment in poor areas.
2. Input Frequency Range 45 ~ 55Hz, to ensure the fuel generator can access all kinds of stability to meet user requirements for use on the oil machine.
Optional accessories:
Heat exchanger & Air Conditioner
The environment which require higher IP level, we use heat exchanger to effectively reduce the temperature of box inside and improve IP protection level .
Heater and temperature controller:
In response to low temperature climate impact of batteries
and UPS, we adopt ajustable heating device to ensure the
UPS and battery life of normal use.
Technical Specifications:
Model | 1KVA | 2KVA | 3KVA | 6KVA | 10KVA |
Range voltage | 220/230/240VAC | ||||
Frequency | 50Hz/62Hz | ||||
Input | |||||
Voltage range | 115~295VAC(±3VAC) | 176~297VAC(±3VAC) | |||
Frequency Range | 50Hz (46~54 Hz) ; 60Hz (56~64 Hz) | ||||
Soft Start | 0~100% 5sec | ||||
Power factor | 0.98 | ||||
Output | |||||
Voltage Precision | 220/230/240VAC(1±2%)AC | ||||
Frequency Precision | 50Hz/62Hz±0.05Hz | ||||
Power factor | 0.7/0.8(optional) standard 0.7 | ||||
Wave Distortion | Linear load<3% Non-linear load<6% | ||||
Overload capability | Overload(110~150%)for 30 seconds,then automatically transfer to bypass.When load is normal,it can automatically transfer to normal mode | ||||
Crest Factor | 3:1 | ||||
Transfer time | 0ms (AC to DC) | ||||
battery | 36VDC | 72VDC | 96VDC | 240VDC | 240VDC |
Charging current | 4A/8A(optional) | 4A/8A(optional) | 4A/8A(optional) | 4.2A | 4.2A |
Internal Battery Caoacity | (38/65/80/100AH) optional | ||||
Panel display | |||||
LED | Load level/Battery level ,Battery indicator,Utility power,Inverter ,Bypass,Overload ,Fault | ||||
Communications | |||||
Communications interface | RS232 SNMP card(optional) | ||||
Work Environment | |||||
Temperature | -40~55ºC | ||||
Humidity | 0~95%(Non-condensing | ||||
Storage Temperature | -25ºC~55ºC | ||||
Elevation | <1500m | ||||
Physical Characteristics | |||||
Weight(KG)N.W | 85 | 125 | 125 | 150 | 150 |
Dimensions:(WxDxH)mm | 613*640*954 | 650*753*1227 | 650*753*1227 | 940*940*1770 | 940*940*17 |