Precision Equipment Modular UPS System High Stability Three Phase 30 - 300KVA
Description:
CNM330 series is modular online UPS for sensitive equipment. The single cabinet power rating covers from 10KVA to 300KVA which delivers the best of combination of reliability, hot-swappable and flexibility. With the latest IGBT three-level technology and DSP control, CNM330 achieves a high input power factor, low THDi Modular design with N+X redundancy and online hot swapping ,easy to expand the capacity Full DSP control of high stability, reliability and safety Integrated IGBT module with improved performance and reduced size
Application:
Application IDC(Internet Data Center)
Computing center
ISP (Internet Service Provider )
Telecom , Finance, bank and securities , Tax
Hospital system , industrial automation
Precision equipment, etc.
Working principle:
Modular UPS use double conversion on-line structure, including the rectifier, inverter, battery charger, control circuit, the input and output battery connector breaker. Have function that is input power factor compensation. All modules can be online hot-swappable, provide the highest level of availability, and maintainability.
If one power module failure will not affect the system normal working, power module can be online hot-swappable all power module parallel is managed by the control board, in accordance with the unified parameters running, one power module fault can be automatically exit parallel system, will not cause harm to the whole parallel system.
Modular UPS system use independent static bypass module, do not use multiple static bypass structure, avoid caused overload damage modules because of multiple bypass module uneven current when UPS turn to bypass working. The module parallel output voltage accuracy is±1%, parallel circulation current< 1%.
Static bypass module contains bypass static switch only, excluded static switch of the main circuit output; therefore, replacing static bypass module will not cause the system power down or transfer manual maintenance bypass, which can realize online hot-swap replacement.
Rich Management Interface
Advanced battery management
Data recorder:
Every 10 ms records a core electrical data, and in Fault occurs, the freezing failure 1 to 1.5 before work. The core of the cycle frequency electrical data Accurately record the cause of failure, to help the accident diagnosis and accurate positioning Rapid diagnosis to improve maintainability, the data will be recorded before a failure or overload occur.
Advanced self-diagnosis:
Technical Specifications:
Model | CNM330 20-300KVA | |
Capacity | 20-300KVA | |
Main Input | ||
Input Voltage | 380V/400V/415V | |
Input Frequency Range | 50/60Hz | |
Power Factor | Full load>0.99 ,Half load >0.98 | |
THDi | THDi<3% | |
Input Power Soft-start Function | 5-30s settable | |
Input Voltage Ranges | 228V-476V;-20%~25% at Full load ; linear derating at -25% ~- 40%; can take 70% load at -40% | |
Frequency Range | 40-70HZ | |
Battery | ||
Battery Voltage | ±240VDC(Default),12V Battery 30~40pcs can be choose | |
Charge Voltage Accuracy | ±1% | |
Bypass | ||
Bypass Input Voltage | 380/400/415VAC 3-phase 4-wire | |
Voltage Range | Default value is -20%~+15%; -40%, -30%, -10% ~ +10%, +15% , other ranges can be set via software | |
Overload Capacity | Long term at 135% rated load ,150%<load<180% more than 10 min, load>1000% 100ms | |
Output | ||
Inverter Output Voltage | 380/400/415VAC 3-phase 4-wire | |
Voltage Accuracy | ±0.5% ( balanced load ) , ±1% ( unbalanced load ) | |
THDV | THDV<1% (linear load) , THDV<3% (nonlinear load) | |
Power Factor | 0.9 | |
Three Phase Angle Accuracy | 120°± 0.5° | |
Current Crest Ratio | 3:1 | |
Overload Capacity | 110%1h,125%10mins,150%1mins,>150%200ms | |
Transfer Time | 0ms,15ms (Eco Mode) | |
System | ||
Frequency | 50Hz/60Hz (Settable) | |
Mains Synchronization Range | ±2Hz(Default value), adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz | |
Protection Level | IP20 | |
Operation Temperature | 0-40ºC | |
Storage Temperature | -25ºC~70ºC ( without battery) | |
Humidity | 0-95% (no-condensing) | |
Noise(dB) | 55-62dB,Adjusted with load | |
Weight | module:PM20 | 20KVA power module : 35KG |
module:PM30 | 30KVA power module : 35KG | |
module:PM40 | 40KVA power module : 35KG | |
Dimension (W x D x H)mm | 3 module cabinet | 600X900X1135 |
5 module cabinet(5 battery cabinet option) | 600X1100X2070/ | |
6 module cabinet | 600X900X1535 | |
10 module cabinet | 900X900X2080 | |
power module | 440X650X132(3U)(10KVA/20KVA/30KVA) |
(Optional South America 208V must be derating use)
Consnant Modular UPS in hospital