CNM330 Series Modular Online UPS
Technical Specifications
Model | CNM330 20-300KVA | |
Capacity | 20-300KVA | |
Main Input | ||
Input Voltage | 380V/400V/415V | |
Input Frequency Range | 50/60Hz | |
Power Factor | Full load>0.99 ,Half load >0.98 | |
THDi | THDi<3% | |
Input Power Soft-start Function | 5-30s settable | |
Input Voltage Ranges | 228V-476V;-20%~25% at Full load ; linear derating at -25% ~- 40%; can take 70% load at -40% | |
Frequency Range | 40-70HZ | |
Battery | ||
Battery Voltage | ±240VDC(Default),12V Battery 30~40pcs can be choose | |
Charge Voltage Accuracy | ±1% | |
Bypass | ||
Bypass Input Voltage | 380/400/415VAC 3-phase 4-wire | |
Voltage Range | Default value is -20%~+15%; -40%, -30%, -10% ~ +10%, +15% , other ranges can be set via software | |
Overload Capacity | Long term at 135% rated load ,150%<load<180% more than 10 min, | |
Output | ||
Inverter Output Voltage | 380/400/415VAC 3-phase 4-wire | |
Voltage Accuracy | ±0.5% ( balanced load ) , ±1% ( unbalanced load ) | |
THDV | THDV<1% (linear load) , THDV<3% (nonlinear load) | |
Power Factor | 0.9 | |
Three Phase Angle Accuracy | 120°± 0.5° | |
Current Crest Ratio | 3:1 | |
Overload Capacity | 110%1h,125%10mins,150%1mins,>150%200ms | |
Transfer Time | 0ms,15ms (Eco Mode) | |
System | ||
Frequency | 50Hz/60Hz (Settable) | |
Mains Synchronization Range | ±2Hz(Default value), adjustable with step of 0.5Hz within range of +/- 0.5Hz - 3Hz | |
Protection Level | IP20 | |
Communication Ports | RS232,RS485,dry contact, SNMP card, EPO, generator port | |
System efficiency | >96% at load above 50%, >95% at load above 25% | |
Operation Temperature | 0-40ºC | |
Storage Temperature | -25ºC~70ºC ( without battery) | |
Humidity | 0-95% (no-condensing) | |
Noise(dB) | 55-62dB,Adjusted with load | |
Weight | module:PM10 | 10KVA power module : 20KG |
module:PM20 | 20KVA power module : 35KG | |
module:PM30 | 30KVA power module : 35KG | |
Dimension (W x D x H)mm | 3 module cabinet | 600X900X1135 |
5 module cabinet(5 battery cabinet option) | 600X1100X2070/ | |
6 module cabinet | 600X900X1535 | |
10 module cabinet | 900X900X2080 | |
power module | 440X650X132(3U)(10KVA/20KVA/30KVA) |
(Optional South America 208V must be derating use)
CNM330 series is a modular online UPS for sensitive equipment. The single cabinet power rating covers from 10KVA to 300KVA which delivers the best of combination of reliability, hot-swappable and flexibility. With the latest IGBT three-level technology and DSP control, CNM330 achieves a high input power factor, low THDi Modular design with N+X redundancy and online hot swapping ,easy to expand the capacity Full DSP control of high stability, reliability and safety Integrated IGBT module with improved performance and reduced size
Application:
Application IDC(Internet Data Center)
Computing center
ISP (Internet Service Provider )
Telecom , Finance, bank and securities , Tax
Hospital system , industrial automation
Precision equipment, etc.
Features:
■ Superior energy saving :
■ Easy-to-install:
■ Easy-to-maintain:
■ Easy-to-modify:
■ Extra large LCD that can display 12 language (Chinese ,English ,Russian, French ,Spanish and so on)
■ Provide large LCD touch screen (optional)
■ Each UPS modules provide 4.5KW charge capacity. equivalent to 10 to 12A
■ Advanced DSP full digital control technologies realize higher system stability, online capacity expansion and maintenance
■ Advanced distributed active parallel technology realizes parallel operation of 4 UPS units and online capacity expansion without centralized bypass cabinet
■ Adaptive to severe power grid environment due to extra wide input voltage and frequency ranges
■ Intelligent battery management maintains battery automatically to prolong the battery life
■ The machine system for modular structure, consists of 1 to 10 module's biggest single module to 30kw
■ UPS power module supporting hot swappable, capacity upgrade extremely simple.
■ Super ability for overload and short circuit, ensure the system stability and safety under the limit state of system
Working Pricipal
MOdularUPSusedoubleconversionon-linestructure, including rectifier, inverter, battery charger, control circuit, the input and the output battery connector breaker. have function that is input power factor compensation. All modules can be online hot-swappable, providing the highest level of availability, and maintainability.
If one power modular failure will not affect the system normal working, power module can be online hot-swappable all power module paralel is managed by the control board, in accourdance with the unified parameters running, one power module fault can be automatically exit parallel system, will not cause harm to the whole parallel system.
Modular UPS system use independent static bepass module, do not use multiple static bypass structure, avoid caused overload damage modules because of multiple bypass module uneven current when UPS turn to bypass working. The module parallel output volage accuracy is ±1%, parallel circulation current<1%.
Static bypass module contains bypass static switch only, excluded static switch of the amain circuit output; therefore, replacing static bypass modulewill not cause the system power down or transfer manual maintenance bypass, which can realize online hot-swap replacement.