Transfer Time ≤ 10msUPS Uninterrupted Power Supply Off Line 12V / 24V Batt.
Our Advantages:
Specification:
| Technical specification | ||||||||||||||
| Model | 500VA | 800VA | 1000VA | 1200VA | ||||||||||
| Input | 220Vac 50Hz, 3.6A Max | 220Vac 50Hz, 5.7A Max | 220Vac 50Hz, 7.1A Max | 220Vac 50Hz, 8.5A Max | ||||||||||
| Output power | 220Vac 50Hz, 2.3A Max | 220Vac 50Hz, 3.6A Max | 220Vac 50Hz, 4.5A Max | 220Vac 50Hz, 5.4A Max | ||||||||||
| Capacity | 500VA/300W | 800VA/480W | 1000VA/600W | 1200VA/720W | ||||||||||
| Input electrical features | ||||||||||||||
| Rated voltage | 220Vac | |||||||||||||
| Utility voltage range | (140~290)±5Vac | |||||||||||||
| Input power factor | 0.98 | 220VAC,full R load | ||||||||||||
| Input frequency | 50/60Hz | Auto select | ||||||||||||
|
Autoselect (Input frequency) |
The nominal frequence is configured according to measured input frequence during the unit starting. | |||||||||||||
| If measured frequence is > 55Hz, nominal frequence setting will be 60Hz | ||||||||||||||
| If measured frequence is ≤ 55Hz, nominal frequence setting will be 50Hz | ||||||||||||||
| Mains frequency range | (40~70)±1Hz | |||||||||||||
| Generator | Support generator input | Generator rating≥2*UPS rating | ||||||||||||
| Input current(Max) | 3.6A Max | 5.7A Max | 7.1A Max | 8.1A Max | ||||||||||
| Auto restart | Support | When the mains recovers if the UPS is shutdown for battery low or remote shutdown | ||||||||||||
| Output electrical features | ||||||||||||||
| Rated voltage | 220Vac | |||||||||||||
| Output voltage range | 220Vac±10%(Line mode); 220Vac± 5%(battery mode) | |||||||||||||
| Output capacity | 500VA/ 300W | 800VA/ 480W | 1000VA/ 600W | 1200VA/ 720W | ||||||||||
| Output Power Factor | 0.6 | |||||||||||||
| Output current(Max) | 2.3A Max | 3.6A | 4.5A Max | 5.4A Max | ||||||||||
| Output wave | Sine wave (Line mode); Square wave (battery mode) | |||||||||||||
| Output frequency (Line mode) | Synch with mains input | |||||||||||||
| Output frequency (battery mode) | (50/60)±1Hz (Frequency self-adapt system) | |||||||||||||
| Transfer time | ≤10ms | |||||||||||||
|
Overload protection |
110% < Load ≤ 120%, buzzer beeps ; output shuts off in 5 mins, and buzzer beeps continuously. Load > 120%, output shuts off, buzzer beeps continuously. |
|||||||||||||
|
Short circuit (battery mode) |
Output shuts off, buzzer beeps continuously. | |||||||||||||
| Batteries features | ||||||||||||||
| Sealed Lead-acid Batteries Maintenance of Free | ||||||||||||||
| Rated battery voltage | 12VDC | 12VDC | 24VDC | 24VDC | ||||||||||
| Amount/Capacity | 1PC/ 12V7AH | 1PC/ 12V9AH | 2PCS/ 12V7AH | 2PCS/ 12V9AH | ||||||||||
| Backup time | > 6Mins (Half load) | |||||||||||||
| Low battery voltage | ≤11V | ≤22V | ||||||||||||
| Battery shutdown voltage | 10V±0.5V | 20V±0.5V | ||||||||||||
| Battery overvoltage protection | 14.5V±0.5V | 29V±0.5V | ||||||||||||
| Charger voltage | 13.7V±0.5V | 27.4V±0.5V | ||||||||||||
| Charging current | 0.5A | |||||||||||||
| Shutdown automatically charge | Yes | |||||||||||||
| Lights and alarms | ||||||||||||||
| Line mode, Battery replacement, Battery mode, Fault mode, Battery mode, Low battery voltage, Over load | Green led flash when it was in the off-mode charging | |||||||||||||
| Communication interface | ||||||||||||||
| Intelligent RS-232, Intelligent USB | Optional | |||||||||||||
| Monitoring software, line of communication | Gaving together with machine | |||||||||||||
| Communication interface | ||||||||||||||
| RJ45, RJ11/12 | Optional | |||||||||||||
| Environment | ||||||||||||||
| Operating temperatures | 0℃~40℃ | |||||||||||||
| Altitude | <1000M | |||||||||||||
| Noise | ≤35dB (1m from front panel) | |||||||||||||
| Storage temperatures | -15℃~45℃ | |||||||||||||
| Relative humidity | 0%~90%(No condensation water) | |||||||||||||
| Cooling | Natural | |||||||||||||
| Appear | ||||||||||||||
| LED/LCD | LED displays UPS status | |||||||||||||
| Standard | ||||||||||||||
| Safety | GB 4943.1-2011 | |||||||||||||
| Transportation | ||||||||||||||
| Drop test | GB-T4857-18 | |||||||||||||
| Vibration test | B-WR1-129(GB-T14715-93) | |||||||||||||
| Machinery features | ||||||||||||||
| Size L×W×H(mm) | 295x90x140 | 329X90X145 | 345x122x190 | |||||||||||
| Net weight (kg) | 4.2 | 5.4 | 7.9 | 9 | ||||||||||