Send Message
Shenzhen Consnant Technology Co., Ltd. 86-755-29772322 sales@consnant.com
Expandable Commercial Ups Battery Backup , 200KVA Three Phase Online Ups Unit

Expandable Commercial Ups Battery Backup , 200KVA Three Phase Online Ups Unit

  • High Light

    online double conversion ups

    ,

    server battery backup

  • Input Voltage Range
    400VAC ±20%
  • Frequency Range
    45-65Hz
  • Soft Start
    0-100% In10"
  • Bypass Input Standard Features
    Back Feed Protection; Split Bypass Line
  • Batteries Type
    Maintenance-free Lead-acid VRLA AGM / GEL;NICd
  • Battery Voltage
    384VDC
  • AC Ripple Voltage
    <1%
  • Place of Origin
    Shenzhen, China
  • Brand Name
    CONSNANT
  • Certification
    CE, ISO9001, ISO14001
  • Model Number
    CNG330
  • Minimum Order Quantity
    1
  • Price
    Negotiable
  • Packaging Details
    Export Standard Package
  • Delivery Time
    30days after receiving 30% deposit
  • Payment Terms
    T/T, L/C, Western Union
  • Supply Ability
    2000 pieces per year

Expandable Commercial Ups Battery Backup , 200KVA Three Phase Online Ups Unit

CNG330 Series Low Frequency Online UPS 10-200KVA
 


Model:CNG330 10-200KVA(3Ph/3Ph)
Nominal Input Voltage: 380/400/415VAC
Output Power Factor:0.8
 

 
Model power CNG330 10-200KVA
10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA
Capacity 8KW 12 KW 16 KW 24 KW 32 KW 48 KW 64 KW 80 KW 96KW 128 KW 160 KW
Input
Rated voltage 400 Vac three-phase
Voltage range ±20%
Frequency range 45-65Hz
Power factor >0.92with harmonic filter
Current harmonic distortion <5%with harmonic filter
Soft Start 0-100% in10"
Bypass Input
Rated voltage 400Vac single-phase
Permitted voltage range ±15%(selectable from ±10% to ±25% from front panel)
Rated frequency 50/60Hz
Permitted frequency range ±2%(selectable from ±1% to ±5% from front panel)
Standard features Back Feed protection; split bypass line
Batteries
Type Maintenance-free lead-acid VRLA AGM / GEL;NICd
Battery voltage 384VDC 480VDC
Maximum recharge current(A) 0.2×C10
AC ripple voltage <1%
Inverter Output
Number of phases 3+N
Rated voltage(V) 400Vac
Regulation of the output voltage 380~424Vac phase/neutral(from control panel)

Crest factor
(Ipeak / Irms)

3:1
Static stability ±1%
Dynamic stability ±5%
Frequency 50/60Hz configurable
Overload 110% 125% 150% of the rated current for 5h/10'/1'
Frequency stability ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present
Remote signaling Volt free contacts
Remote controls EPO and Bypass
Communication RS232 + romote contacts
Operation temperature 0ºC/ + 40ºC
Relative humidity <95% non condensing
Noise 54dBA at 1m 50-65dBA at 1m
Protection degree IP20
Efficiency smart mode up to 98%
Compliance Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC)
 

 
Application:


Servers,
Local area Network(LAN),
Data centers,
Telecommunications,
Electro-medical equipment


High intelligence and reliable power supply:

 

  • Maximum protection for vital mission-critical networks, security applications (electro- medical)and industrial applications thanks to its outstanding mechanical and electrical design.
  • The load is powered continuously by the inverter with a filtered, stabilized and regulated sine wave supply. The input and output EMI filters considerably increase the immunity of the load to mains disturbances and surges.
  • On-line double conversion technology (VFI) with isolation transformer on the inverter output.
  • Watch & Save 3000 software as standard and can be remotely monitored using the Power Net Guard system from anywhere in the world.
  • Additional battery extension packs allow the standard battery routine to be extended up to several hours.


Maximum battery care:

  • Battery deep discharge protection;
  • Temperature compensating charger;
  • Built-in automatic and manual battery test feature.


Simple to install:


Capability to install the UPS into any distribution system(neutral not required on rectifier input);
Capability to separate the rectifier/bypass power networks and to power these from two separate sources, without Galvanic isolation (Necessary on UPS without an output transformer).


High reliability:
 

  • Extremely high short-circuit current to ensure compatibility with the most difficult transformer applications (lighting, drives and industrial processes)
  • An isolation transformer on the inverter output;
  • Full microprocessor control with no-break static and manual bypasses;
  • IGBT technology.


Other characteristics:

 

  • 0.8 power factor, suitable for powering ICT and Industrial loads;
  • High level diagnostics: event log with 128 messages, states, measurements and alarms - available from the built-in LCD with several languages;


Back feed protection: To avoid energy feeding back into the mains supply cause a fault occur.


Maximum reliability and availability:The UPS continue to work in parallel even if one of the interconnecting communication cables is disconnected (CLOOSED LOOP).


Low consumption level:selectable Economy Mode efficiencies >98% 


Expandabilityparallel up to 8 units and can be expanded any time to suit power requirements without influencing the initial investment.
 
Sales Service: 
 
1. 2% spares together with shipment for urgent issue.
2. All of the necessary documents such as drawing, manaul etc.
3. We will provide the online service by mail
4. Online Guide will be provied all the time. We also can desptach engineer to assist you solve the problem if necessary. But you are requested to pay for the cost of ticket, hotel etc.

 
Expandable Commercial Ups Battery Backup , 200KVA Three Phase Online Ups Unit 0