CNG330 Series Low Frequency Online UPS 10-200KVA
Model:CNG330 10-200KVA(3Ph/3Ph)
Nominal Input Voltage: 380/400/415VAC
Output Power Factor:0.8
Frequency: 45-65Hz
Standard features: Back Feed protection; split bypass line
Battery voltage: 384VDC
Model power | CNG330 10-200KVA | |||||||||||
10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA | ||
Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | 96KW | 128 KW | 160 KW | |
Input | ||||||||||||
Rated voltage | 400 Vac three-phase | |||||||||||
Voltage range | ±20% | |||||||||||
Power factor | >0.92with harmonic filter | |||||||||||
Current harmonic distortion | <5%with harmonic filter | |||||||||||
Soft Start | 0-100% in10" | |||||||||||
Bypass Input | ||||||||||||
Rated voltage | 400Vac single-phase | |||||||||||
Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||||
Rated frequency | 50/60Hz | |||||||||||
Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||||
Batteries | ||||||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||||
480VDC | ||||||||||||
Maximum recharge current(A) | 0.2×C10 | |||||||||||
AC ripple voltage | <1% | |||||||||||
Inverter Output | ||||||||||||
Number of phases | 3+N | |||||||||||
Rated voltage(V) | 400Vac | |||||||||||
Regulation of the output voltage | 380~424Vac phase/neutral(from control panel) | |||||||||||
Crest factor (Ipeak / Irms) |
3:1 | |||||||||||
Static stability | ±1% | |||||||||||
Dynamic stability | ±5% | |||||||||||
Frequency | 50/60Hz configurable | |||||||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||||
Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||||||
Remote signaling | Volt free contacts | |||||||||||
Application:
Servers,
Local area Network(LAN),
Data centers,
Telecommunications,
Electro-medical equipment
High intelligence and reliable power supply:
Minimum impact on supplies easy sources:
Input current distortion <4% with filter with sinusoidal absorption to remove the risk of resonance with other input supply users or phase shift capacitor sets. The absorbed current distortion is independent of input supply parameters such as impedance. This enable CNG330 to deliver maximum performance levels regardless of the installation environment. With these input features CNG330 can achieve significant savings in terms of sizing and power supply sources isolation transformers and generators over less sophisticated power systems.
Maximum battery care:
Simple to install:
Capability to install the UPS into any distribution system(neutral not required on rectifier input);
Capability to separate the rectifier/bypass power networks and to power these from two separate sources, without Galvanic isolation (Necessary on UPS without an output transformer).
High reliability:
Extremely high short-circuit current to ensure compatibility with the most difficult transformer applications (lighting, drives and industrial processes) and an isolation transformer on the inverter output;
Full microprocessor control with no-break static and manual bypasses;
IGBT technology.
Back feed protection:
To avoid energy feeding back into the mains supply cause a fault occur.
Maximum reliability and availability:
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.The UPS continue to work in parallel even if one of the interconnecting communication cables is disconnected (CLOOSED LOOP).
Low consumption level:
Selectable Economy Mode efficiencies >98%, which means it can be used in stable electrical environments to provide power supply continuity when the mains fail.
Advance communication
Expandability:
The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded any time to suit power requirements without influencing the initial investment.
Other characteristics:
Remote controls | EPO and Bypass | |||||||||||
Operation temperature | 0ºC/ + 40ºC | |||||||||||
Relative humidity | <95% non condensing | |||||||||||
Noise | 54dBA at 1m | 50-65dBA at 1m | ||||||||||
Protection degree | IP20 | |||||||||||
Efficiency smart mode | up to 98% | |||||||||||
Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC) |