CNG310 Series Low Frequency Online UPS 10-100KVA
Snapshot:
Model:CNG310 10-100KVA(3Ph/1Ph)
Nominal Input Voltage: 380/400/415VAC
Output Power Factor:0.8
Technical parameter of CNG310 series:
Model power | CNG310 10KVA | |||||||||
10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | |||
Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | ||
Input | ||||||||||
Rated Voltage | 80-300 Vac three-phase | |||||||||
Voltage Range | ±20% | |||||||||
Frequency Range | 45-65Hz | |||||||||
Power Factor | >0.92with harmonic filter | |||||||||
Current Harmonic Distortion | <5%with harmonic filter | |||||||||
Soft Start | 0-100% in10" | |||||||||
Bypass Input | ||||||||||
Rated Voltage | 230Vac single-phase | |||||||||
Permitted Voltage Range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||
Rated Frequency | 50/60Hz | |||||||||
Permitted Frequency Range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||
Standard Features | BackFeed protection; split bypass line | |||||||||
Batteries | ||||||||||
Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||
Battery Voltage | 384VDC | |||||||||
Maximum Recharge Current(A) | 0.2 X C10 | |||||||||
AC Ripple Voltage | <1% | |||||||||
Inverter Output | ||||||||||
Number of Phases | 1 | |||||||||
Rated Voltage(V) | 48Vac single-phase | |||||||||
Regulation of the Output Voltage | 48Vac phase/neutral(from control panel) | |||||||||
Crest Factor(Ipeak/Irms) | 3:1 | |||||||||
Static Stability | ±1% | |||||||||
Dynamic Stability | ±5% | |||||||||
Frequency | 50/60Hz configurable | |||||||||
Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||
Frequency Stability | ±0.05% on mains failure | |||||||||
Remote Signaling | Volt free contacts | |||||||||
Remote Controls | EPO and Bypass | |||||||||
Communication | RS232 + remote contacts | |||||||||
Operation Temperature | 0ºC/ + 40ºC | |||||||||
Relative Humidity | <95% non condensing | |||||||||
Color | Light gray (RAL 7035) | |||||||||
Noise | 54dBA at 1m | 60dBA at 1m | 65dBA at 1m | |||||||
Protection Degree | IP20 | |||||||||
Efficiency Smart Mode | up to 98% | |||||||||
Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC) |
Application:
Servers,
Local area Network(LAN),
Data centers,
Telecommunications,
Electro-medical equipment
Maximum battery care:
Battery deep discharge protection;
Temperature compensating charger;
Built-in automatic and manual battery test feature.
High reliability:
Extremely high short-circuit current to ensure compatibility with the most difficult transformer applications (lighting,drives and industrial processes) and an isolation transformer on the inverter output;
Full microprocessor control with no-break static and manual bypasses;
IGBT technology.
Other characteristics:
Suitable for powering ICT and Industrial loads;
High level diagnostics: event log with 128 messages, states,measurements and alarms - available from the built-in LCD with several languages;
Back feed protection:
To avoid energy feeding back into the mains supply cause a fault occur.
Maximum reliability and availability:
Connect up to 6 units in parallel or N+1 redundancy, even of different power ratings.The UPS continue to work in parallel even if one of the interconnecting communication cables is disconnected (CLOOSED LOOP).
Low consumption level:
CNG310 can achieve efficiencies >98% thanks to selectable Economy Mode which can be used in stable electrical environments to provide power supply continuity when the mains fail.
Advance communication:
Compatible with TeleNetGuard for remote maintenance;
Watch & Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows 2008, Vista,2003, XP; Mac OS X,Linux, Novell and most popular Unix operating systems;
The UPS is supplied with a cable for direct connection to the PC(Plug and Play);
RS232 double Serial port;Installation slot for an Emergency Power Off (EPO) interface to allow the UPS to be switched off remotely in an emergency;
Generator interface: enables desynchronisation of the UPS output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charge.
Expandability:
The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded any time to suit power requirements without influencing the initial investment.