        Technical Parameter:
| Capacity | Power Module | 30KVA/27KW | ||||
| Input | Input type | 3 Phase, 4 Wires + Grounding | ||||
| Rated Voltage | 380/400V/415VAC | |||||
| Voltage Range | 208~478VAC | |||||
| Frequency Range | 40~70Hz | |||||
| Power Factor | ≥0.99 | |||||
| Bypass Range | Bypass protection highest voltage:+15%(available to choose +5%,+10%,+25%) | |||||
| Bypass protection lowest voltage:-45%(available to choose -20%,-30%) | ||||||
| Bypass protection frequency range:±10% | ||||||
| Input current harmonic | ≤3% (100% nonlinear load) | |||||
| Output | Output type | 3 Phase, 4 Wires + Grounding | ||||
| Rated Voltage | 380/400V/415VAC | |||||
| Power Factor | 0.9 | |||||
| Voltage accuracy | ±2% | |||||
| Output Frequency | AC Mode | Synchronize with the input;when the main power frequency over the range of ±10%(available to choose ±1%,±2%,±4%,±5%),output frequency will be 50×(±0.2)Hz | ||||
| Battery Mode | (50/60±0.2%)Hz | |||||
| Load Crest Ratio | 3:01 | |||||
| Transfer time | AC to Bypass: 0ms(tracking);AC to Battery:0ms | |||||
| Overload Ability | Load ≤110%,60min,≤125%,continue working 10min,≤150% continue working 1min,≥150% off | |||||
| Output voltage distortion | ≤2% linear load | |||||
| ≤5% non linear load | ||||||
| Efficiency | Normal Mode ≥92% | |||||
| Interface | UPS cabinet | RS232,RS485,2 pieces Intelligent Slot,dry contact | ||||
| Battery | Battery Voltage | ±192V±204V±216V±228V±240V DC; (32 pcs,34 pcs,36 pcs,38 pcs,40 pcs are optional) | ||||
| Charge current | UPS Cabinet | 45Amax | 75Amax | 150Amax | ||
| Power Module | 15Amax | |||||
| Working Environments | Operation Temperature | 0℃~40℃ | ||||
| Humidity | 0~95% no-codensing | |||||
| Storage Temperature | -25℃~55℃ | |||||
| Altitude | < 1500m | |||||
| WXDXH(mm) | Power Module | 443*580*131 | ||||
| Weight(Kg) | Power Module | 33 | ||||
| Standard | CE,EN/IEC 62040-2,EN/IEC 62040-1-1,YD/T1095-2008 | |||||