Send Message
Shenzhen Consnant Technology Co., Ltd. 86-755-29772322 sales@consnant.com
Hybrid Off Grid Solar Power Inverter 48v To 230v Pure Sine Wave Output 1-12kw

Hybrid Off Grid Solar Power Inverter 48v To 230v Pure Sine Wave Output 1-12kw

  • High Light

    solar power 3 phase inverter

    ,

    solar panel dc to ac inverter

  • Charger Mode
    MPPT
  • Input Voltage Range
    120/230VAC
  • Transfer Time
    AC To DC: 20ms(max); DC To AC: 15ms(max)
  • Output Short Circuit Protection
    Current Limit (Fault After 10s)
  • Surge Rating(10s)
    1:3(VA)
  • Protections
    Low Battery, Over Charging, Over Load, Over Temp
  • Power Saver
    Load≤25W(Enabled On "P/S Auto"Setting Of Remote Control)
  • Place of Origin
    Shenzhen, China
  • Brand Name
    CONSNANT
  • Certification
    CE, ISO9001, ISO14001
  • Model Number
    CNS110
  • Minimum Order Quantity
    10
  • Price
    Negotiable
  • Packaging Details
    Each unit in one carton
  • Delivery Time
    5-7 days for sample order, 7-15 days for mass production
  • Payment Terms
    30% T/T inadvance, L/C, Western Union
  • Supply Ability
    50000 pieces per year

Hybrid Off Grid Solar Power Inverter 48v To 230v Pure Sine Wave Output 1-12kw

Hybrid Off Grid Solar Power Inverter 48v To 230v Pure Sine Wave Output 1-12kw

 

 

Key Features:

1. AC/Solar Charging Off Grid Hybrid Inverter.

2. LED/LCD display, Enhanced functions setting via LCD, Man-machine intelligent design

3. Built-in 40A/60A optional MPPT solar charger controller.

4. LCD shows the solar capacity.

5. 5 stages adjustable AC charging current. AC charging also can be closed

6. AC/DC priority modes can be set.

7. Generator restart signal. (Dry contact)

8. 3 times peak power. Strong loading capacity.

9. Overload, output short-circuit protection.

 

 

Product Description:

 

CNS110 Series Hybrid Inverter is designed to serve as a backup power supply for AC loads. The input power of CNS110 Series hybrid inverter comes from PV system and AC grid which not only supply power to AC loads but also charge the battery bank when the power from AC grid or AC generator is present(also known as Line Mode).

In the event of the AC grid (or AC generator) outage, the AC loads can be alternatively powered by PV system(if the illumination is sufficient) and the battery bank.

The following illusions show basic applications for CNS110 Series Hybrid Inverter

 

Hybrid Off Grid Solar Power Inverter 48v To 230v Pure Sine Wave Output 1-12kw 0

 


CNS110 Series Technical Specifications:

 

 

Model CNS110 1KW-12KW
Line Mode Specification: LV Model(1-6KW) HV Model(1-12KW)
Input Voltage Input Voltage Waveform Sinusoidal(utility or generator)
Nominal Input Voltage LV 12Vac HV 230Vac
Low Line Disconnect Normal:85Vac±4% Normal: 184 Vac±4%
Wide: 80 Vac±4% Wide: 135 Vac±4%
Low Line Reconnect Normal:95Vac±4% Normal:194Vac±4%
Wide: 85 Vac±4% Wide: 145Vac±4%
High Line Disconnect Normal:136Vac±4% Normal:263Vac±4%
Wide: 140 Vac±4% Wide: 263Vac±4%
High Line Reconnect Normal:131Vac±4% Normal:253Vac±4%
Wide: 135 Vac±4% Wide: 253 Vac±4%
Max AC Input Voltage 150V rms 270V rms
Input Frequency

Nominal Input

Frequency

50Hz/60Hz(Auto detection)
     

Low Line

Frequency Re-connect

51+0.3Hz for 60Hz;

41+0.3Hz for 50Hz;

Low Line

Frequency Disconnect

50+0.3Hz for 60Hz;

40+0.3Hz for 50Hz;

High Line

Frequency Reconnect

64+0.3Hz for 60Hz;

54+0.3Hz for 50Hz;

High Line

Frequency Disconnect

65+0.3Hz for 60Hz;

55+0.3Hz for 50Hz;

Main Function Output Voltage Waveform As same as input waveform
Over-load Protection(SMPS load) Air switch

Output Short

Circuit Protection

Air switch

Max Bypass

Overload Current

40A/50A